FICIX - PLANNED WORK ANNOUNCEMENT 0801 Planned work ID: 0801 Release date: 15-May-2008 Site: FICIX1 (Otaniemi, Espoo) Type of maintenance: UPS replacement Impact to services: None Schedule Start: 15-May-2008 11:20 EET End: 15-Dec-2008 11:26 EET Service Provider: Forte Netservices Emergency contact info: FICIX / Jorma Mellin: +358 50 994 4762 General enquiries: contact@ficix.fi SUMMARY: FICIX1 UPS replacement maintenance *COMPLETED* DETAILS: FICIX1 site had one faulty UPS device (battery failure). Switch itself has four (4) power supplies and they are connected to two (2) separate UPS devices. The switch in current configuration require two power supplies to remain in function. As both UPS devices have reached 5 years operational time both of them are now replaced with new ones. Work was carried out by disconnecting and replacing one UPS device at a time. No impact to peering traffic was detected. Management connection to switch failed for 6 minutes and therefore also statistics collection were down during that timeframe. --- EOF